Synchronizing - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
12.1.7.3
Technical Manual
OperationSC = Enabled
TSTSC
BLKSC
OR
BLOCK
AND
VDiffSC
AND
Bus voltage >80%
of GblBaseSelBus
AND
Line voltage >80%
of GblBaseSelLine
FreqDiffA
PhaseDiffA
voltageDifferenceValue
frequencyDifferenceValue
phaseAngleDifferenceValue
ANSI08000018 V2 EN
Figure 149:
Simplified logic diagram for the Auto Synchronism function

Synchronizing

When the function is set to OperationSynch = Enabled the measuring will be performed.
The function will compare the values for the bus and line voltage with internally preset
values that are set to be 80% of the set value of GlbBaseSelBus and GlbBaseSelLine,
which is a supervision that the voltages are both live. Also the voltage difference is
checked to be smaller than the internally preset value 0.10, which is a p.u value of set
voltage base values. If both sides are higher than the preset values and the voltage
Note! Similar logic for Manual Synchrocheck.
AND
AND
0-tSCA
0
50 ms
0
0
AND
80 ms
PhaseDiff > 60°
PhaseDiff < 5°
Section 12
Control
AND
AUTOSYOK
AND
VOKSC
VDIFFSC
1
FRDIFFA
1
PHDIFFA
1
VDIFFME
FRDIFFME
100 ms
INADVCLS
AND
ANSI08000018-2-en.vsd
325