ABB REG650 Technical Manual page 402

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 14
Monitoring
Name
Values (Range)
PDbRepInt
1 - 300
PZeroDb
0 - 100000
PHiLim
-2000.0 - 2000.0
PLowLim
-2000.0 - 2000.0
PLowLowLim
-2000.0 - 2000.0
PLimHyst
0.000 - 100.000
QDbRepInt
1 - 300
QZeroDb
0 - 100000
QHiHiLim
-2000.0 - 2000.0
QHiLim
-2000.0 - 2000.0
QLowLim
-2000.0 - 2000.0
QLowLowLim
-2000.0 - 2000.0
QLimHyst
0.000 - 100.000
PFDbRepInt
1 - 300
PFZeroDb
0 - 100000
PFHiHiLim
-1.000 - 1.000
PFHiLim
-1.000 - 1.000
PFLowLim
-1.000 - 1.000
PFLowLowLim
-1.000 - 1.000
PFLimHyst
0.000 - 100.000
VDbRepInt
1 - 300
VZeroDb
0 - 100000
VHiHiLim
0.0 - 200.0
VHiLim
0.0 - 200.0
VLowLim
0.0 - 200.0
VLowLowLim
0.0 - 200.0
VLimHyst
0.000 - 100.000
IDbRepInt
1 - 300
IZeroDb
0 - 100000
IHiHiLim
0.0 - 500.0
IHiLim
0.0 - 500.0
Table continues on next page
396
Unit
Step
Default
Type
1
10
m%
1
500
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
Type
1
10
m%
1
500
%SB
0.1
150.0
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
Type
1
10
m%
1
500
-
0.001
1.000
-
0.001
0.800
-
0.001
-0.800
-
0.001
-1.000
%
0.001
5.000
Type
1
10
m%
1
500
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%
0.001
5.000
Type
1
10
m%
1
500
%IB
0.1
150.0
%IB
0.1
120.0
1MRK 502 043-UUS B
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range (common for
all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range (common for
all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range (common for
all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit in % of UBase
High limit in % of UBase
Low limit in % of UBase
Low Low limit in % of UBase
Hysteresis value in % of range (common for
all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit in % of IBase
High limit in % of IBase
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents