IED and functionality tests
628
Description
3 s
Continuous
Pulse magnetic field immunity
test
Power frequency immunity test
Common mode
Differential mode
Voltage dips and short
interruptionsc on DC power
supply
Voltage dips and interruptions
on AC power supply
Electromagnetic emission tests
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
0.5...30 MHz
Radiated RF-emission
30...230 MHz
230...1000 MHz
Type test value
1000 A/m
100 A/m
1000A/m
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at
power down
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at
power down
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 40 dB(µV/m) quasi peak,
measured at 10 m distance
< 47 dB(µV/m) quasi peak,
measured at 10 m distance
1MRK 502 043-UUS B
Reference
IEC 61000–4–9, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
IEC 60255–11
IEC 61000–4–11
EN 55011, class A
IEC 60255-25