Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 12
Control
12.3.5
Table 208:
SLGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
NrPos
2 - 32
OutType
Pulsed
Steady
tPulse
0.000 - 60.000
tDelay
0.000 - 60000.000
StopAtExtremes
Disabled
Enabled
12.3.6
12.3.7
344

Settings

Unit
Step
-
-
-
1
-
-
s
0.001
s
0.010
-
-
Monitored data
Table 209:
SLGGIO Monitored data
Name
Type
SWPOSN
INTEGER
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs – UP and DOWN. When a signal is received on the
UP input, the block will activate the output next to the present activated output, in
ascending order (if the present activated output is 3 – for example and one operates the
UP input, then the output 4 will be activated). When a signal is received on the DOWN
input, the block will activate the output next to the present activated output, in
descending order (if the present activated output is 3 – for example and one operates
the DOWN input, then the output 2 will be activated). Depending on the output
settings the output signals can be steady or pulsed. In case of steady signals, in case of
UP or DOWN operation, the previously active output will be deactivated. Also,
depending on the settings one can have a time delay between the UP or DOWN
activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a "select before execute" dialog. One can block the function operation,
by activating the BLOCK input. In this case, the present position will be kept and
further operation will be blocked. The operator place (local or remote) is specified
Default
Description
Disabled
Operation Enable/Disable
32
Number of positions in the switch
Steady
Output type, steady or pulse
0.200
Operate pulse duration
0.000
Output time delay
Disabled
Stop when min or max position is reached
Values (Range)
Unit
-
-
1MRK 502 043-UUS B
Description
Switch position as integer
value
Technical Manual