Section 9
Voltage protection
9.3.3
9.3.4
266
Two step residual overvoltage protection ROV2PTOV (59N) function calculates the
residual voltage from the three-phase voltage input transformers or measures it from a
single voltage input transformer fed from a broken delta or neutral point voltage
transformer.
ROV2PTOV (59N) has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.

Function block

ROV2PTOV (59N)
V3P*
TRIP
BLOCK
TRST1
BLK1
TRST2
BLK2
PICKUP
PU_ST1
PU_ST2
ANSI09000273_1_en.vsd
ANSI09000273 V1 EN
Figure 123:
ROV2PTOV (59N) function block
Signals
Table 149:
ROV2PTOV (59N) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 150:
ROV2PTOV (59N) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
General pickup signal
Start signal from step 1
Start signal from step 2
1MRK 502 043-UUS B
Technical Manual