ABB REG650 Technical Manual page 217

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Technical Manual
Q
> Q
If
final
EQUATION1172 V1 EN
(
Q = Q
+ Q
- Q
-
n
n
1
final
EQUATION1173 V1 EN
Q
< Q
If
final
EQUATION1174 V1 EN
(
Q = Q
- Q
n
final
final
EQUATION1175 V1 EN
where:
is the calculated present temperature
Q
n
Q
is the calculated temperature at the previous time step
n-1
is the calculated final (steady state) temperature with the actual current
Q
final
is the time step between calculation of the actual and final temperature
Dt
t
is the set thermal time constant Tau1 or Tau2 for the protected transformer
The calculated transformer relative temperature can be monitored as it is exported from
the function as a real figure HEATCONT.
When the transformer temperature reaches any of the set alarm levels Alarm1 or
Alarm2 the corresponding output signals ALARM1 or ALARM2 are activated. When
the temperature of the object reaches the set trip level which corresponds to continuous
current equal to ITrip the output signal TRIP is activated.
There is also a calculation of the present time to operation with the present current.
This calculation is only performed if the final temperature is calculated to be above the
operation temperature:
æ
Q
t
= - × ç
final
t
ln
ç
operate
Q
è
final
EQUATION1176 V1 EN
The calculated time to trip can be monitored as it is exported from the function as a
real figure TTRIP.
n
æ
ö
D
t
)
-
×
-
t
1
e
ç
÷
-
n
1
è
ø
n
D
t
)
-
- Q
×
t
e
-
n
1
ö
- Q
operate
÷
÷
- Q
ø
n
Section 8
Current protection
(Equation 51)
(Equation 52)
(Equation 53)
(Equation 54)
(Equation 55)
211