Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 14
Monitoring
14.1.2.4
Table 284:
CVMMXN Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
PowMagFact
0.000 - 6.000
PowAngComp
-180.0 - 180.0
k
0.00 - 1.00
SLowLim
0.0 - 2000.0
SLowLowLim
0.0 - 2000.0
SMin
0.0 - 2000.0
SMax
0.0 - 2000.0
SRepTyp
Cyclic
Dead band
Int deadband
PMin
-2000.0 - 2000.0
Table continues on next page
394
Name
Type
PF
REAL
PF_RANGE
INTEGER
ILAG
BOOLEAN
ILEAD
BOOLEAN
V
REAL
V_RANGE
INTEGER
I
REAL
I_RANGE
INTEGER
F
REAL
F_RANGE
INTEGER

Settings

Unit
Step
-
-
-
1
-
-
-
0.001
Deg
0.1
-
0.01
%SB
0.1
%SB
0.1
%SB
0.1
%SB
0.1
-
-
%SB
0.1
Description
Power factor magnitude of deadband value
Power factor range
Current is lagging voltage
Current is leading voltage
Calculated voltage magnitude of deadband value
Calcuated voltage range
Calculated current magnitude of deadband value
Calculated current range
System frequency magnitude of deadband value
System frequency range
Default
Description
Disabled
Disable/Enable Operation
1
Selection of one of the Global Base Value
groups
A, B, C
Selection of measured current and voltage
1.000
Magnitude factor to scale power calculations
0.0
Angle compensation for phase shift between
measured I & V
0.00
Low pass filter coefficient for power
measurement
80.0
Low limit in % of SBase
60.0
Low Low limit in % of SBase
50.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-200.0
Minimum value in % of SBase
1MRK 502 043-UUS B
Technical Manual