Section 6
Differential protection
6.3.5
Table 36:
GENPDIF (87G) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.10 - 1.00
IdUnre
1.00 - 50.00
OpNegSeqDiff
No
Yes
IMinNegSeq
0.02 - 0.40
116
Table 35:
GENPDIF (87G) Output signals
Name
Type
TRIP
BOOLEAN
TRIPRES
BOOLEAN
TRIPUNRE
BOOLEAN
TRNSUNR
BOOLEAN
TRNSSENS
BOOLEAN
PICKUP
BOOLEAN
BLKH
BOOLEAN
OPENCT
BOOLEAN
OPENCTAL
BOOLEAN
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IDMAG_NS
REAL
IBIAS
REAL

Settings

Unit
Step
-
-
IB
0.01
IB
0.01
-
-
IB
0.01
Description
General, common trip signal
Trip signal from restrained differential protection
Trip signal from unrestrained differential protection
Trip signal from unrestrained negative sequence
differential protection
Trip signal from sensitive negative sequence
differential protection
Common pickup signal from any phase
Common harmonic block signal
An open CT was detected
Open CT Alarm output signal. Issued after a delay ...
Fund. freq. differential current, phase A; in primary A
Fund. freq. differential current, phase B; in primary A
Fund. freq. differential current, phase C; in primary A
Negative Sequence Differential current; in primary
Amperes
Magnitude of the common Bias current; in primary
Amperes
Default
Description
Disabled
Operation Disable / Enable
0.25
Section 1 sensitivity, multiple of generator
rated current
10.00
Unrestr. prot. limit, multiple of generator rated
current
Yes
Negative Sequence Differential Enable Off/On
0.10
Neg. sequence curr. limit, as multiple of gen.
rated curr.
1MRK 502 043-UUS B
Technical Manual