ABB REG650 Technical Manual page 575

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Technical Manual
based on the set system frequency. DFTReference set to DFTRefGrpX uses DFT
reference from the selected group block, when own group selected adaptive DFT
reference will be used based on the calculated signal frequency from own group.
DFTReference set to External DFT Ref will use reference based on input signal
DFTSPFC.
Settings DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available. However, if it is
necessary to use frequency adaptive DFT (DFTReference set to other
than default, referring current measuring SMAI) when no voltages are
available, note that the MinValFreqMeas setting is still set in reference
to VBase (of the selected GBASVAL group). This means that the
minimum level for the current amplitude is based on VBase. For
example, if VBase is 20000, the resulting minimum amplitude for
current is 20000 * 10% = 2000.
MinValFreqMeas: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of the voltage in the selected Global Base voltage
group (GBASVAL:n, where 1<n<6).
Below example shows a situation with adaptive frequency tracking with one reference
selected for all instances. In practice each instance can be adapted to the needs of the
actual application.
Section 17
Basic IED functions
569