Section 7
Impedance protection
7.4.2
7.4.3
7.4.4
7.4.5
Table 63:
LEPDIS Group settings (basic)
Name
Values (Range)
RLd
0.05 - 3000.00
LdAngle
5 - 85
162

Functionality

Heavy load transfer is common in many power networks and may make fault
resistance coverage difficult to achieve. In such a case, Load encroachment (LEPDIS)
function can be used to prevent operation of the of the underimpedance measuring
zones during heavy loads.
Function block
LEPDIS
I3P*
DLECND
V3P*
BLOCK
ANSI10000119-1-en.vsd
ANSI10000119 V1 EN
Figure 76:
LEPDIS function block
Signals
Table 61:
LEPDIS Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 62:
LEPDIS Output signals
Name
Type
DLECND
INTEGER
Settings
Unit
Step
ohm/p
0.01
Deg
1
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
Description
Binary coded starts from load encroachment
Default
Description
1.00
Load resistive reach in ohm/phase
38
Load encroachment inclination of load
angular sector