Signals

Table 337:
SPGGIO Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Operation principle
Upon receiving a signal at its input, IEC61850 generic communication I/O functions
(SPGGIO) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. To get the signal, PCM600 must be used to define which
function block in which equipment or system should receive this information.
IEC 61850 generic communication I/O functions 16
inputs SP16GGIO
Identification
Function description
IEC 61850 generic communication I/O
functions 16 inputs
Functionality
IEC 61850 generic communication I/O functions 16 inputs (SP16GGIO) function is
used to send up to 16 logical signals to other systems or equipment in the substation.
Default
Description
0
Block of function
0
Input status
IEC 61850
IEC 60617
identification
identification
SP16GGIO
-
1MRK 502 043-UUS B
ANSI/IEEE C37.2
device number
-
Technical Manual