Section 7
Impedance protection
150
Table 56:
Advanced general settings for the function OOSPPAM (PSP1-)
Parameter
Range
StartAngle
90.0 - 130.0
TripAngle
15.0 - 90.0
Table 57:
Basic parameter group settings for the function OOSPPAM (PSP1-)
Parameter
Range
Operation
Off
On
OperationZ1
Off
On
ReachZ1
1.00 - 100.00
OperationZ2
Off
On
tBreaker
0.000 - 1.000
Table 58:
Advanced parameter group settings for the function OOSPPAM (PSP1-)
Parameter
Range
NoOfSlipsZ1
1 - 20
NoOfSlipsZ2
1 - 60
tReset
1.000 - 60.000
Step
Default
Unit
0.1
110.0
0.1
60.0
Step
Default
Unit
-
Off
-
On
0.01
50.00
-
On
0.001
0.000
Step
Default
Unit
1
1
1
3
0.001
6.000
1MRK 502 043-UUS B
Description
Deg
Angle between two rotors
to get the start signal, in
deg
Deg
Maximum rotor angle to
allow trip signals, in deg
Description
-
Operation Off / On
-
Operation Zone1 On / Off
-
Percentage part of total
forward impedance;
defines Z1 reach
-
Operation Zone2 On / Off
s
Breaker opening time;
use default 0s value if it is
unknown
Description
-
Number of pole-slips in
zone 1 required to get
zone 1 trip
-
Number of pole-slips in
zone 2 required to get
zone 2 trip
s
Time without any slip
required to completely
reset function
Technical Manual