Section 16
Station communication
16.2.3
16.2.4
Table 394:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
GOOSE
Front
LAN1
520
interoperates with other IEC 61850-compliant IEDs, tools, and systems and
simultaneously reports events to five different clients on the IEC 61850 station bus.
The event system has a rate limiter to reduce CPU load. The event channel has a quota
of 10 events/second. If the quota is exceeded the event channel transmission is blocked
until the event changes is below the quota, no event is lost.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the fibre-optic multimode LC connector (100BASE-FX).
The IED supports SNTP and IRIG-B time synchronization methods with a time-
stamping resolution of 1 ms.
Ethernet based: SNTP and DNP3
With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 time synchronization methods with a time
stamping resolution of 5 ms.

Communication interfaces and protocols

Table 393:
Supported station communication interfaces and protocols
Protocol
Ethernet
IEC 61850–8–1
DNP3
IEC 60870-5-103
● = Supported
Settings
Unit
Step
-
-
-
-
100BASE-FX LC
Glass fibre (ST connector)
-
Default
Description
Disabled
LAN1
1MRK 502 043-UUS B
Serial
EIA-485
-
Operation Disabled/Enabled
Port for GOOSE communication