ABB REG650 Technical Manual page 102

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 6
Differential protection
96
sequence current contributions, respectively, defined by expression shown in
equation 23. It performs a directional comparison between these two phasors. Taking
into account the phase rotation transformation the relative phase displacement between
the two negative sequence current phasors is calculated. In case of three-winding
power transformers, a little more complex algorithm is applied, with two directional
tests. The overall directional characteristic of the internal/external fault discriminator is
shown in figure 33, where the directional characteristic is defined by two setting
parameters:
1.
IMinNegSeq
2.
NegSeqROA
120 deg
If one or the
other of
currents is too
low, then no
measurement
is done, and
120 degrees
is mapped
180 deg
External
fault
region
IEC05000188 V3 EN
Figure 33:
Operating characteristic of the internal/external fault discriminator
In order to perform directional comparison of the two phasors their magnitudes must
be high enough so that one can be sure that they are due to a fault. On the other hand,
in order to guarantee a good sensitivity of the internal/external fault discriminator, the
value of this minimum limit must not be too high. Note that, in order to enhance
stability at higher fault currents, the relatively very low threshold value IminNegSeq is
dynamically increased at currents higher than normal currents: if the bias current is
higher than 110% of IBase current, then 10% of the bias current is added to the
IminNegSeq. Only if magnitudes of both negative sequence current contributions are
90 deg
Internal/external
fault boundary
IMinNegSeq
270 deg
en05000188-3-en.vsd
1MRK 502 043-UUS B
NegSeqROA
(Relay
Operate
Angle)
0 deg
Internal
fault
region
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents