1MRK 502 043-UUS B
Table 259:
TIMERSET Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
t
0.000 - 90000.000
13.3.1.9
Technical Manual
Function block
TIMERSET
INPUT
OFF
IEC09000290-1-en.vsd
IEC09000290 V1 EN
Figure 178:
TIMERSET function block
Signals
Table 257:
TIMERSET Input signals
Name
Type
INPUT
BOOLEAN
Table 258:
TIMERSET Output signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
Settings
Unit
Step
-
-
s
0.001

AND function block

Identification
Function description
AND function block
Functionality
The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs.
ON
Default
Description
0
Input signal
Description
Output signal, pick-up delayed
Output signal, drop-out delayed
Default
Disabled
0.000
IEC 61850
identification
AND
Section 13
Description
Operation Disabled/Enabled
Delay for settable timer n
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Logic
375