Section 7
Impedance protection
138
IEC10000176 V2 EN
Figure 60:
Mho, offset mho characteristic for Zone 1 with setting parameters
Z1Fwd, Z1Rev and ImpedanceAng
The measuring loops can be time delayed individually by setting the parameter tZx
(where x is 1-3 depending on selected zone). For instantaneous operation set the
parameter tZx to 0.00 s for the particular zone. To enable the zone, the operation mode
for the zone, x (where x is 1-3 depending on selected zone), has to be set to Enable-
Zone.
The function are blocked in the following ways:
Activating of input BLOCK blocks the whole function.
Activating of the input BLKZ (fuse failure) blocks all output signals.
The activation of input signal BLKZ can be made by external or internal fuse failure
function.
X
ImpedanceAng
IEC10000176-2-en.vsd
1MRK 502 043-UUS B
R
Technical Manual