ABB REG650 Technical Manual page 639

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Technical Manual
A1
51
t=0
t=t
1
ANSI05000132 V1 EN
Figure 265:
Selectivity steps for a fault on feeder B1
where:
t=0
is The fault occurs
t=t
is Protection B1 trips
1
t=t
is Breaker at B1 opens
2
t=t
is Protection A1 resets
3
In the case protection B1 shall operate without any intentional delay (instantaneous).
When the fault occurs the protections pickup to detect the fault current. After the time
t
the protection B1 send a trip signal to the circuit breaker. The protection A1 starts its
1
delay timer at the same time, with some deviation in time due to differences between
the two protections. There is a possibility that A1 will start before the trip is sent to the
B1 circuit breaker.
At the time t
the circuit breaker B1 has opened its primary contacts and thus the fault
2
current is interrupted. The breaker time (t2 - t1) can differ between different faults. The
maximum opening time can be given from manuals and test protocols. Still at t
timer of protection A1 is active.
At time t
the protection A1 is reset, i.e. the timer is stopped.
3
In most applications it is required that the delay times shall reset as fast as possible
when the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type of
delayed reset time of the overcurrent function. This can be the case in the following
applications:
Time inverse characteristics
B1
51
t=t
t=t
2
3
Section 21
Feeder
Time axis
en05000132_ansi.vsd
the
2
633