Outputs - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 18
IED physical connections
18.3
18.3.1
586
Table 464:
Binary inputs X339, 3U full 19"
Terminal
Description
X339-1
- for input 1
X339-2
Binary input 1 +
X339-3
-
X339-4
Common - for inputs 2-3
X339-5
Binary input 2 +
X339-6
Binary input 3 +
X339-7
-
X339-8
Common - for inputs 4-5
X339-9
Binary input 4 +
X339-10
Binary input 5 +
X339-11
-
X339-12
Common - for inputs 6-7
X339-13
Binary input 6 +
X339-14
Binary input 7 +
X339-15
-
X339-16
Common - for inputs 8-9
X339-17
Binary input 8 +
X339-18
Binary input 9 +

Outputs

Outputs for tripping, controlling and signalling
Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for
controlling circuit breakers.
Each signal connector terminal is connected with one 14 or 16 Gauge wire. Use 12 or
14 Gauge wire for CB trip circuit.
The connected DC voltage to outputs with trip circuit supervision
(TCM) must have correct polarity or the trip circuit supervision
TCSSCBR function will not operate properly.
1MRK 502 043-UUS B
PCM600 info
Hardware module
Hardware channel
instance
BIO_6
BI1
BIO_6
BI1
BIO_6
BI2
BIO_6
BI3
BIO_6
BI4
BIO_6
BI5
BIO_6
BI6
BIO_6
BI7
BIO_6
BI8
BIO_6
BI9
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents