Energizing inputs

Table 480:
Energizing inputs
Description
Rated frequency
Operating range
Current inputs
Rated current, I
Thermal withstand capability:
Continuously
For 1 s
For 10 s
Dynamic current withstand:
Half-wave value
Input impedance
Voltage inputs
Rated voltage, V
Voltage withstand:
Continuous
For 10 s
Burden at rated voltage
*) max. 350 A for 1 s when COMBITEST test switch is included.
1) Residual current
2) Phase currents or residual current
Binary inputs
Table 481:
Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption/input
Threshold voltage
Value
50/60 Hz
Rated frequency ± 5 Hz
1)
0.1/0.5 A
n
4 A
100 A
20 A
250 A
<100 mΩ
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
n
420 V rms
450 V rms
<0.05 VA
Value
Maximum input voltage 300 V DC
24...250 V DC
1.6...1.8 mA
<0.38 W
15...221 V DC (parametrizable in the range in steps of
1% of the rated voltage)
1MRK 502 043-UUS B
2)
1/5 A
20 A
500 A *)
100 A
1250 A
<20 mΩ
Technical Manual