Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
12.11.4
Table 232:
I103GENCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 127
PulseLength
0.000 - 60.000
InfNo
32 - 239
12.12
12.12.1
12.12.2
12.12.3
Technical Manual

Settings

Unit
Step
-
1
s
0.001
-
1
IED commands with position and select for IEC
60870-5-103 I103POSCMD
Functionality
I103POSCMD has double-point position indicators that are getting the position value
as an integer (for example from the POSITION output of the SCSWI function block)
and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE); as per standard, 0 and 3
values of the position are not supported.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type
of control)
Function block
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286-1-en.vsd
IEC10000286 V1 EN
Figure 166:
I103POSCMD function block
Signals
Table 233:
I103POSCMD Input signals
Name
Type
BLOCK
BOOLEAN
POSITION
INTEGER
SELECT
BOOLEAN
Default
Description
1
Function type (1-255)
0.400
Pulse length
32
Information number for command output
(1-255)
Default
Description
0
Block of command
0
Position of controllable object
0
Select of controllable object
Section 12
Control
359