Goose Function Block To Receive A Measurand Value Goosemvrcv; Identification; Functionality - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

1MRK 505 394-UEN A
18.4.9
18.4.9.1
18.4.9.2
Line differential protection RED650 2.2 IEC
Technical manual
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and communication
error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the integer values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive a measurand value
GOOSEMVRCV

Identification

Function description
GOOSE function block to receive a
measurand value

Functionality

GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via
GOOSE.
Station communication
Data Value
Data Valid
Updated
1
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Freeze
0
Updated
1
Updated
1
Freeze
0
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
Section 18
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
ANSI/IEEE C37.2
device number
-
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3
651