Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
7.4.7
Technical Manual
X
A
R
AB
I ³
3
0.05
0
&
³
×
3
I
0.2
I
0
phmax
BLOCK
I <
3
0.1
0
OR
<
×
3
I
0.4
I
0
phmax
ANSI10000226 V2 EN
Figure 78:
Phase-to-phase AB operating conditions (residual current criteria)
Special attention is paid to correct phase selection at evolving faults. A DLECND
output signal is created as a combination of the load encroachment characteristic and
current criteria, refer to figure 78. This signal can be configured to PHSEL functional
input signals of the distance protection zone and this way influence the operation of the
phase-to-phase zone measuring elements and their phase related pickup and tripping
signals.

Technical data

Table 65:
LEPDIS technical data
Function
Load encroachment criteria:
Load resistance, forward and
reverse
Safety load impedance angle
Reset ratio
&
&
&
10 ms
0
&
0
20 ms
Range or value
(1.00–3000.00) Ω/phase
(5-85) degrees
105% typically
Section 7
Impedance protection
Block
DLECND
Bool to
&
integer
ANSI10000226-2-en.vsd
Accuracy
± 5.0% static accuracy
± 2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
Current range: (0.5-30) x I
n
-
n
165