SSIML OutputSignals

Table 358:
Output signals for the function block SSIML (LM1-)
Signal
LEVEL
LVL_ALM
LVL_LO
TEMP
TEMP_ALM
TEMP_LO
Settings
SSIML Settings
Table 359:
Basic parameter group settings for the function SSIML (LM1-)
Parameter
Range
Operation
Off
On
LevelAlmLimit
0.00 - 25.00
LevelLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tLevelAlarm
0.000 - 60.000
tLevelLockOut
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetLevelAlm
0.000 - 60.000
tResetLevelLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
Description
Level service value
Level below alarm level
Level below lockout level
Temperature of the insulation medium
Temperature above alarm level
Temperature above lockout level
Step
Default
Unit
-
Off
0.01
5.00
0.01
3.00
0.01
30.00
0.01
30.00
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
Section 14
Monitoring
Description
-
Operation Off / On
-
Alarm setting for level
-
Level lockout setting
-
Temperature alarm level
setting of the medium
-
Temperature lockout
level of the medium
s
Time delay for level alarm
s
Time delay for level
lockout indication
s
Time delay for
temperature alarm
s
Time delay for temperture
lockout
s
Reset time delay for level
alarm
s
Reset time delay for level
lockout
s
Reset time delay for
temperture lockout
s
Reset time delay for
temperture alarm
481