ABB REG650 Technical Manual page 641

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Technical Manual
For inverse time characteristics a time will be initiated when the current reaches the set
pickup level. From the general expression of the characteristic the following can be seen:
æ
P
(
)
æ
ö
i
× ç
-
×
t
B td
ç
÷
ç
op
è
ø
Pickupn
è
EQUATION1642 V1 EN
where:
t
is the operating time of the protection
op
The time elapsed to the moment of trip is reached when the integral fulfils according to
equation 115, in addition to the constant time delay:
t
æ
ö
P
æ
ö
i
ò
ç
÷
-
×
³
ç
÷
C
dt
A td
ç
÷
è
ø
Pickupn
è
ø
0
EQUATION1643 V1 EN
For the numerical protection the sum below must fulfil the equation for trip.
æ
ö
( )
n
P
æ
ö
å
i j
ç
÷
D ×
-
³
t
ç
÷
C
ç
÷
è
ø
Pickupn
è
ø
=
j
1
EQUATION1644 V1 EN
where:
j = 1
Dt
n
i (j)
For inverse time operation, the inverse time characteristic is selectable. Both the IEC
and ANSI/IEEE standardized inverse time characteristics are supported.
Time inverse characteristics
ö
÷ =
-
×
C
A td
÷
ø
×
×
A td
is the first protection execution cycle when a fault has been
detected, that is, when
i
>
1
Pickupn
EQUATION1646 V1 EN
is the time interval between two consecutive executions of the
protection algorithm,
is the number of the execution of the algorithm when the trip time
equation is fulfilled, that is, when a trip is given and
is the fault current at time j
Section 21
(Equation 114)
(Equation 115)
(Equation 116)
635