Section 12
Control
12.2
12.2.1
12.2.2
12.2.2.1
12.2.2.2
334
Function
Operate time for energizing
function
Minimum time to accept
synchronizing conditions
Maximum allowed frequency rate
of change

Apparatus control

Functionality
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and grounding switches within a bay. Permission to operate is
given after evaluation of conditions from other functions such as interlocking,
synchronism check, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
Bay control QCBAY
Identification
Function description
Bay control
Functionality
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the
bay.
Range or value
80 ms typically
(0.000-60.000) s
(0.000-0.500) Hz/s
IEC 61850
IEC 60617
identification
identification
QCBAY
-
1MRK 502 043-UUS B
Accuracy
-
± 0.5% ± 10 ms
± 10.0 mHz/s
ANSI/IEEE C37.2
device number
-
Technical Manual