1MRK 502 043-UUS B
Name
Values (Range)
ILowLim
0.0 - 500.0
ILowLowLim
0.0 - 500.0
ILimHyst
0.000 - 100.000
FrDbRepInt
1 - 300
FrZeroDb
0 - 100000
FrHiHiLim
0.000 - 100.000
FrHiLim
0.000 - 100.000
FrLowLim
0.000 - 100.000
FrLowLowLim
0.000 - 100.000
FrLimHyst
0.000 - 100.000
VMagComp5
-10.000 - 10.000
VMagComp30
-10.000 - 10.000
VMagComp100
-10.000 - 10.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
14.1.2.5
Technical Manual
Unit
Step
%IB
0.1
%IB
0.1
%
0.001
Type
1
m%
1
Hz
0.001
Hz
0.001
Hz
0.001
Hz
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
Deg
0.001
Deg
0.001
Deg
0.001
Monitored data
Table 286:
CVMMXN Monitored data
Name
Type
S
REAL
P
REAL
Q
REAL
PF
REAL
Table continues on next page
Default
Description
80.0
Low limit in % of IBase
60.0
Low Low limit in % of IBase
5.000
Hysteresis value in % of range (common for
all limits)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping
65.000
High High limit (physical value)
63.000
High limit (physical value)
47.000
Low limit (physical value)
45.000
Low Low limit (physical value)
5.000
Hysteresis value in % of range (common for
all limits)
0.000
Magnitude factor to calibrate voltage at 5% of
Vn
0.000
Magnitude factor to calibrate voltage at 30%
of Vn
0.000
Magnitude factor to calibrate voltage at 100%
of Vn
0.000
Magnitude factor to calibrate current at 5% of
In
0.000
Magnitude factor to calibrate current at 30%
of In
0.000
Magnitude factor to calibrate current at 100%
of In
0.000
Angle calibration for current at 5% of In
0.000
Angle calibration for current at 30% of In
0.000
Angle calibration for current at 100% of In
Values (Range)
Unit
-
MVA
-
MW
-
MVAr
-
-
Section 14
Monitoring
Description
Apparent power magnitude of
deadband value
Active power magnitude of
deadband value
Reactive power magnitude of
deadband value
Power factor magnitude of
deadband value
397