Section 8
Current protection
8.4.6
8.4.7
210

Monitored data

Table 89:
TRPTTR (49) Monitored data
Name
Type
TTRIP
REAL
TTRIPCAL
INTEGER
TRESCAL
INTEGER
TRESLO
REAL
HEATCONT
REAL
I-MEASUR
REAL
Operation principle
The sampled analog phase currents are pre-processed and for each phase current the
true RMS value of each phase current is derived. These phase current values are fed to
the Thermal overload protection, two time constants (TRPTTR, 49).
From the largest of the three phase currents a relative final temperature (heat content)
is calculated according to the expression:
2
æ
ö
I
Q
= ç
÷
ç
÷
final
I
è
ø
ref
EQUATION1171 V1 EN
where:
I
I
ref
If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current a pickup output signal PICKUP is activated.
The actual temperature at the actual execution cycle is calculated as:
Values (Range)
Unit
-
-
-
-
-
-
-
-
-
%
-
%
is the largest phase current
is a given reference current
1MRK 502 043-UUS B
Description
Estimated time to trip (in min)
Calculated time status to trip:
not active/long time/active
Calculated time status to
reset: not active/long time/
active
Estimated time to reset of the
function (in min)
Percentage of the heat
content of the transformer
Current measured by the
function in % of the rated
current
(Equation 50)
Technical Manual