Function Block - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
17.14.3.2
17.14.3.3
17.14.3.4
17.14.3.5
Technical Manual

Function block

DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
IEC09000134 V1 EN
Figure 260:
DOSLAN1 function block
Signals
Table 455:
DOSLAN1 Output signals
Name
Type
LINKUP
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Settings
The function does not have any parameters available in the local HMI or PCM600.
Monitored data
Table 456:
DOSLAN1 Monitored data
Name
Type
State
INTEGER
Quota
INTEGER
IPPackRecNorm
INTEGER
IPPackRecPoll
INTEGER
IPPackDisc
INTEGER
Table continues on next page
Description
Ethernet link status
Frame rate is higher than normal state
Frame rate is higher than throttle state
Values (Range)
Unit
0=Off
-
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
%
-
-
-
-
-
-
Section 17
Basic IED functions
Description
Frame rate control state
Quota level in percent 0-100
Number of IP packets
received in normal mode
Number of IP packets
received in polled mode
Number of IP packets
discarded
579

Advertisement

Table of Contents
loading

Table of Contents