Goose Function Block To Receive A Measurand Value Goosemvrcv; Identification; Functionality; Function Block - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 15
Station communication
15.7
15.7.1
15.7.2
15.7.3
15.7.4
474
The implementation for IEC61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive a measurand
value GOOSEMVRCV

Identification

Function description
GOOSE function block to receive a
measurand value

Functionality

GOOSEMVRCV is used to receive measured value from the sender using
IEC61850 protocol over GOOSE.

Function block

GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
IEC10000251 V1 EN
Figure 234:
GOOSEMVRCV function block

Signals

Table 391:
GOOSEMVRCV Input signals
Name
Type
BLOCK
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
Default
Description
0
Block of function
1MRK 502 034-UEN -
ANSI/IEEE C37.2
device number
-
Technical Manual