Table 126:
NS2PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tAlarm
0.00 - 6000.00
OpStep1
Disabled
Enabled
I2-1>
3 - 500
CurveType1
Definite
Inverse
t1
0.00 - 6000.00
tResetDef1
0.000 - 60.000
K1
1.0 - 99.0
t1Min
0.000 - 60.000
t1Max
0.00 - 6000.00
ResetMultip1
0.01 - 20.00
OpStep2
Disabled
Enabled
I2-2>
3 - 500
t2
0.00 - 6000.00
tResetDef2
0.000 - 60.000
Technical Manual
Table 125:
NS2PTOC (46I2) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
ALARM
BOOLEAN
NSCURR
REAL

Settings

Unit
Step
-
-
s
0.01
-
-
%IB
1
-
-
s
0.01
s
0.001
s
0.1
s
0.001
s
0.01
-
0.01
-
-
%IB
1
s
0.01
s
0.001
Description
Common trip signal
Trip signal for step 1
Trip sognal for step 2
Common start signal
Pickup signal for step 1
Pickup signal for step2
Alarm signal
Negative sequence current in primary amps
Default
Description
Disabled
Disable/Enable Operation
3.00
Time delay for alarm ( operated by pick up
signal) in seconds
Enabled
Enable execution of step 1
10
Step 1 Neg. Seq. Current pickup level, in %
of IBase
Definite
Selection of definite or inverse time-
characteri. for step 1
10.00
Definite time delay for trip of step 1, in sec
0.000
Time delay for reset of definite timer of step 1,
in sec
10.0
Neg. seq. capability value of generator for
step 1, in sec
5.000
Minimum trip time for inverse delay of step 1,
in sec
1000.00
Maximum trip delay for step 1, in sec
1.00
Reset multiplier for K1, defines reset time of
inverse curve
Enabled
Enable execution of step 2
10
Step 2 Neg. Seq. Current pickup level, in %
of IBase
10.00
Definite time delay for trip of step 2, in sec
0.000
Time delay for reset of definite timer of step 2,
in sec
Section 8
Current protection
239