Section 14
Monitoring
14.14.4.2
14.14.5
14.14.5.1
478

SSIMG OutputSignals

Table 354:
Output signals for the function block SSIMG (GM01-)
Signal
PRESSURE
PRES_ALM
PRES_LO
TEMP
TEMP_ALM
TEMP_LO
Settings
SSIMG Settings
Table 355:
Basic parameter group settings for the function SSIMG (GM01-)
Parameter
Range
Operation
Off
On
PressAlmLimit
0.00 - 25.00
PressLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tPressureAlarm
0.000 - 60.000
tPressureLO
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetPressAlm
0.000 - 60.000
tResetPressLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
Description
Pressure service value
Pressure below alarm level
Pressure below lockout level
Temperature of the insulation medium
Temperature above alarm level
Temperature above lockout level
Step
Default
Unit
-
Off
0.01
5.00
0.01
3.00
0.01
30.00
0.01
30.00
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
1MRK 502 043-UUS B
Description
-
Operation Off / On
-
Alarm setting for pressure
-
Pressure lockout setting
-
Temperature alarm level
setting of the medium
-
Temperature lockout
level of the medium
s
Time delay for pressure
alarm
s
Time delay for pressure
lockout indication
s
Time delay for
temperature alarm
s
Time delay for temperture
lockout
s
Reset time delay for
pressure alarm
s
Reset time delay for
pressure lockout
s
Reset time delay for
temperture lockout
s
Reset time delay for
temperture alarm
Technical Manual