binary inputs, are routed. It has a single trip output (TRIP) for connection to one or
more of the IEDs binary outputs, as well as to other functions within the IED requiring
this signal.
ANSI05000789 V2 EN
Figure 168:
Simplified logic diagram for three pole trip
Lockout can be activated either by activating the input (SETLKOUT) or automatically
from the trip input by setting AutoLock to Enabled. A Lockout condition will be
indicated by activation of the output (CLLKOUT). If lockout has been activated it can
be reset by activating the input (RSTLKOUT) or via the HMI.
If TripLockout is set to Enabled an active Lockout will latch the three-phase trip
output. In this way if both AutoLock and TripLockout are set to Enabled the trip will
always be three-phase and sealed in.

Technical data

Table 239:
SMPPTRC (94) technical data
Function
Trip action
Timers
Trip matrix logic TMAGGIO
Identification
Function description
Trip matrix logic
Range or value
3-ph
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
TMAGGIO
-
Section 13
Logic
Accuracy
-
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
363