Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Impedance protection
7.1.7
140
I
X
AB·
× ZxFwd
I
AB
-
× ZxRev
I
AB
ANSI09000174 V2 EN
Figure 61:
Simplified offset mho characteristic and voltage vectors for phase A-to-
B fault.
Operation occurs if 90≤β≤270.

Technical data

Table 45:
ZGCPDIS (21G) technical data
Function
Number of zones
Forward positive sequence impedance
Reverse positive sequence impedance
Angle for positive sequence impedance,
Timers
Operate time
Reset ratio
=
-
Vcomp
1
V
(
I
AB
ß
V
Vcomp
I
AB·
Range or value
3
(0.005-3000.000) Ω/
phase
(0.005-3000.000) Ω/
phase
(10-90) degrees
(0.000-60.000) s
25 ms typically
105% typically
1MRK 502 043-UUS B
× ZxFwd
)
AB
=
+
× ZxRev
2
V
(
I
)
AB
AB
R
ANSI09000174_2_en.vsd
Accuracy
-
± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x
V
n
Current range: (0.5-30) x I
Angle: at 85 degrees
-
-
± 0.5% ± 10 ms
-
-
Technical Manual
n