Section 14
Monitoring
14.3.6.9
452

Analog signals

Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for
external analog signals from analog input modules via preprocessing function blocks
(SMAI) and summation block (3PHSUM). The last 10 channels may be connected to
internally calculated analog signals available as function block output signals (phase
differential currents, bias currents and so on).
External analog
signals
Internal analog signals
IEC05000653 V2 EN
Figure 206:
Analog input function blocks
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated according to
the cycle time of the specific function. If a function is running at lower speed than the
base sampling rate, Disturbance recorder will use the latest updated sample until a new
updated sample is available.
Application configuration tool (ACT) is used for analog configuration of the
Disturbance report.
SMAI
GRPNAME
AI3P
AI1NAME
AI1
AI2NAME
AI2
AI3NAME
AI3
AI4NAME
AI4
AIN
1MRK 502 043-UUS B
A1RADR
A2RADR
GRPINPUT1
A3RADR
GRPINPUT2
GRPINPUT3
GRPINPUT4
GRPINPUT5
GRPINPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
en05000653-2.vsd
Technical Manual