Pole discrepancy protection CCRPLD (52PD)

Identification
Function description
Pole discrepancy protection
Functionality
Circuit breakers and disconnectors can end up with their phases in different positions
(close-open), due to electrical or mechanical failures. An open phase can cause
negative and zero sequence currents which cause thermal stress on rotating machines
and can cause unwanted operation of zero sequence or negative sequence current
functions.
Normally the affected breaker is tripped to correct such a situation. If the situation
warrants the surrounding breakers should be tripped to clear the unsymmetrical load
situation.
The pole discrepancy function operates based on information from the circuit breaker
logic with additional criteria from unsymmetrical phase currents when required.
Range or value
lBase
(5-200)% of
> 95%
(0.000-60.000) s
35 ms typically
10 ms maximum
IEC 61850
identification
CCRPLD
Section 8
Current protection
Accuracy
± 1.0% of I
at I £ I
n
n
± 1.0% of I at I > I
n
-
± 0.5% ±10 ms
-
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
52PD
PD
SYMBOL-S V1 EN