1MRK 502 043-UUS B
6.1.2.3
Technical Manual

Signals

Table 22:
T3WPDIF (87T) Input signals
Name
Type
I3PW1CT1
GROUP
SIGNAL
I3PW2CT1
GROUP
SIGNAL
I3PW3CT1
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 23:
T3WPDIF (87T) Output signals
Name
Type
TRIP
BOOLEAN
TRIPRES
BOOLEAN
TRIPUNRE
BOOLEAN
TRNSUNR
BOOLEAN
TRNSSENS
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
BLK2H
BOOLEAN
BLK5H
BOOLEAN
BLKWAV
BOOLEAN
IDALARM
BOOLEAN
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IBIAS
REAL
IDMAG_NS
REAL
Default
Description
-
Three phase current connection winding 1 (W1) CT1
-
Three phase current connection winding 2 (W2) CT1
-
Three phase current connection winding 3 (W3) CT1
0
Block of function
Description
Common trip signal
Trip signal from restrained differential protection
Trip signal from unrestrained differential protection
Trip signal from unrestrained negative sequence
differential protection
Trip signal from sensitive negative sequence
differential protection
General pickup signal
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
General second harmonic block signal
General fifth harmonic block signal
General block signal from waveform criteria
General alarm for sustained differential currents
Magnitude of fundamental frequency differential
current, phase A
Magnitude of fundamental frequency differential
current, phase B
Magnitude of fundamental frequency differential
current, phase C
Magnitude of the bias current, which is common to all
phases
Magnitude of the negative sequence differential current