Identification - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
17.11.1
17.11.2
17.11.3
Table 450:
GBASVAL Non group settings (basic)
Name
Values (Range)
VBase
0.05 - 1000.00
IBase
1 - 50000
SBase
0.050 - 5000.000
17.12
17.12.1
Technical Manual

Identification

Function description
Global base values
Functionality
Global base values function (GBASVAL) is used to provide global values, common
for all applicable functions within the IED. One set of global values consists of values
for current, voltage and apparent power and it is possible to have six different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a single
point for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one out
of the six sets of GBASVAL functions.
Settings
Unit
Step
kV
0.05
A
1
MVA
0.001
Authority check ATHCHCK
Identification
Function description
Authority check
IEC 61850
IEC 60617
identification
identification
GBASVAL
-
Default
Description
132.00
Global base voltage
1000
Global base current
229.000
Global base apparent power
IEC 61850
IEC 60617
identification
identification
ATHCHCK
-
Section 17
Basic IED functions
ANSI/IEEE C37.2
device number
-
ANSI/IEEE C37.2
device number
-
573