Section 14
Monitoring
14.17.3
14.17.4
Table 367:
I103MEAS Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
MaxIa
1 - 99999
MaxIb
1 - 99999
MaxIc
1 - 99999
MaxIN
1 - 99999
MaxVa
0.05 - 2000.00
MaxVb
0.05 - 2000.00
MaxVc
0.05 - 2000.00
MaxVa-Vb
0.05 - 2000.00
MaxVn
0.05 - 2000.00
MaxP
0.00 - 2000.00
MaxQ
0.00 - 2000.00
MaxF
50.0 - 60.0
498

Signals

Table 366:
I103MEAS Input signals
Name
Type
BLOCK
BOOLEAN
I_A
REAL
I_B
REAL
I_C
REAL
IN
REAL
V_A
REAL
V_B
REAL
V_C
REAL
V_AB
REAL
V_N
REAL
P
REAL
Q
REAL
F
REAL
Settings
Unit
Step
-
1
A
1
A
1
A
1
A
1
kV
0.05
kV
0.05
kV
0.05
kV
0.05
kV
0.05
MW
0.05
MVA
0.05
Hz
10.0
Default
Description
0
Block of service value reporting
0.0
Service value for current phase A
0.0
Service value for current phase B
0.0
Service value for current phase C
0.0
Service value for residual current IN
0.0
Service value for voltage phase A
0.0
Service value for voltage phase B
0.0
Service value for voltage phase C
0.0
Service value for voltage phase-phase A-B
0.0
Service value for residual voltage VN
0.0
Service value for active power
0.0
Service value for reactive power
0.0
Service value for system frequency
Default
Description
1
Function type (1-255)
3000
Maximum current phase A
3000
Maximum current phase B
3000
Maximum current phase C
3000
Maximum residual current IN
230.00
Maximum voltage for phase A
230.00
Maximum voltage for phase B
230.00
Maximum voltage for phase C
400.00
Maximum voltage for phase-phase A-B
230.00
Maximum residual voltage VN
1200.00
Maximum value for active power
1200.00
Maximum value for reactive power
50.0
Maximum system frequency
1MRK 502 043-UUS B
Technical Manual