ABB REG650 Technical Manual page 237

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Technical Manual
Chosen current
phasors
Complex
power
Chosen voltage
calculation
phasors
ANSI06000438 V2 EN
Figure 106:
Simplified logic diagram of the power protection function
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 116.
Table 116:
Complex power calculation
Mode
Set value:
A, B, C
Arone
PosSeq
AB
BC
Table continues on next page
P
Derivation of
S( angle)
S( composant)
in Char angle
Q
Formula used for complex power calculation
=
×
S
V
I
A
EQUATION2055-ANSI V1 EN
=
S
V
AB
EQUATION2056-ANSI V1 EN
= ×
S
3
V
PosSeq
EQUATION2057-ANSI V1 EN
=
×
S
V
AB
EQUATION2058-ANSI V1 EN
=
×
S
V
BC
EQUATION2059-ANSI V1 EN
Section 8
Current protection
S( angle) <
t
TRIP 1
Power1
0
PICKUP1
S( angle) <
t
TRIP2
Power2
0
PICKUP2
P = POWRE
Q = POWIM
ANSI06000438-2-en.vsd
*
*
*
+
×
+
×
V
I
V
I
A
B
B
C
C
(Equation 58)
*
*
×
-
×
I
V
I
A
BC
C
(Equation 59)
*
×
I
PosSeq
(Equation 60)
*
*
-
(
I
I
)
A
B
(Equation 61)
*
*
-
(
I
I
)
B
C
(Equation 62)