ABB REG650 Technical Manual page 87

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Name
Values (Range)
ConnectTypeW2
WYE (Y)
Delta (D)
ConnectTypeW3
WYE (Y)
Delta (D)
ClockNumberW2
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ClockNumberW3
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ZSCurrSubtrW1
Disabled
Enabled
ZSCurrSubtrW2
Disabled
Enabled
ZSCurrSubtrW3
Disabled
Enabled
Technical Manual
Unit
Step
Default
-
-
WYE (Y)
-
-
Delta (D)
-
-
0 [0 deg]
-
-
5 [150 deg lag]
-
-
Enabled
-
-
Enabled
-
-
Enabled
Differential protection
Description
Connection type of winding 2: Y-wye or D-delta
Connection type of winding 3: Y-wye or D-delta
Phase displacement between W2 & W1=HV
winding, hour notation
Phase displacement between W3 & W1=HV
winding, hour notation
Enable zero sequence subtraction for W1
side, Off/On
Enable zero sequence subtraction for W2
side, Off/On
Enable zero sequence subtraction for W3
side, Off/On
Section 6
81

Advertisement

Table of Contents
loading

Table of Contents