Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
9.2.8
9.3
9.3.1
9.3.2
Technical Manual

Technical data

Table 148:
OV2PTOV (59) technical data
Function
Operate voltage, low and
high step
Reset ratio
Inverse time
characteristics for low
and high step, see
table
504
Definite time delay, step 1
Definite time delays, step
2
Minimum operate time,
Inverse characteristics
Operate time, pickup
function
Reset time, pickup
function
Critical impulse time
Impulse margin time
Two step residual overvoltage protection ROV2PTOV
(59N)
Identification
Function description
Two step residual overvoltage
protection
Functionality
Residual voltages may occur in the power system during ground faults.
Range or value
VBase
(1-200)% of
>95%
-
(0.00 - 6000.00) s
(0.000-60.000) s
(0.000-60.000) s
30 ms typically at 0 to 2 x V
set
40 ms typically at 2 to 0 x V
set
10 ms typically at 0 to 2 x V
set
15 ms typically
IEC 61850
identification
ROV2PTOV
Section 9
Voltage protection
Accuracy
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
-
See table
504
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
-
-
-
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
59N
3U0>
IEC10000168 V1 EN
n
n
265

Advertisement

Table of Contents
loading

Table of Contents