1MRK 502 043-UUS B
9.5.3
9.5.4
Technical Manual

Function block

STEFPHIZ (59THD)
NEUTVOLT*
TRIP
TERMVOLT*
TRIP3H
52A
TRIP_VN
BLOCK
PICKUP
BLOCK3RD
PU_3H
BLOCKVN
PU_VN
DV3
BV3
ANSI07000033 -3-en.vsd
ANSI07000033 V3 EN
Figure 130:
STEFPHIZ (59THD) function block
Signals
Table 161:
STEFPHIZ (59THD) Input signals
Name
Type
NEUTVOLT
GROUP
SIGNAL
TERMVOLT
GROUP
SIGNAL
52a
BOOLEAN
BLOCK
BOOLEAN
BLOCK3RD
BOOLEAN
BLOCKVN
BOOLEAN
Table 162:
STEFPHIZ (59THD) Output signals
Name
Type
TRIP
BOOLEAN
TRIP3H
BOOLEAN
TRIP_VN
BOOLEAN
PICKUP
BOOLEAN
PU_3H
BOOLEAN
PU_VN
BOOLEAN
DV3
REAL
BV3
REAL
Default
Description
-
Voltage connection neutral side
-
Open-Delta connection on Terminal side
1
Input 1 (TRUE) means breaker between gen. & tr. is
closed
0
Complete block of the stator ground fault protecion
function
0
Block of the 3rd harmonic-based parts of the protection
0
Block of the fund. harmonic-based part of the protection
Description
Main, common trip command
Trip by one of two 3rd harmonic voltage-based prot.
Trip by fund. freq. neutral over-voltage protection
Main, common pick up signal
Start by one of two 3rd harmonic voltage-based prot.
Pick up signal by fund. freq. neutral over-voltage prot.
Diff. between 3rd harm. volt. at both sides of gen.
Bias voltage, a part of UN3
Section 9
Voltage protection
283