Dnp3 Protocol - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Section 16
16.1
16.2
16.2.1
16.2.2
Technical Manual
Station communication

DNP3 protocol

DNP3 (Distributed Network Protocol) is a set of communications protocols used to
communicate data between components in process automation systems. For a detailed
description of the DNP3 protocol, see the DNP3 Communication protocol manual.
IEC 61850-8-1 communication protocol
Identification
Function description
IEC 61850-8-1 communication protocol
Functionality
The IED supports the communication protocols IEC 61850-8-1 and DNP3 over TCP/
IP. All operational information and controls are available through these protocols.
However, some communication functions, for example, horizontal communication
(GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1 communication
protocol.
The IED is equipped with an optical Ethernet rear port for the substation
communication standard IEC 61850-8-1. IEC 61850-8-1 protocol allows intelligent
electrical devices (IEDs) from different vendors to exchange information and
simplifies system engineering. Peer-to-peer communication according to GOOSE is
part of the standard. Disturbance files uploading is provided.
Disturbance files are accessed using the IEC 61850-8-1 protocol. Disturbance files are
available to any Ethernet based application via FTP in the standard Comtrade format.
Further, the IED can send and receive binary values, double point values and measured
values (for example from MMXU functions), together with their quality bit, using the
IEC 61850-8-1 GOOSE profile. The IED meets the GOOSE performance requirements
for tripping applications in substations, as defined by the IEC 61850 standard. The IED
Station communication
IEC 61850
IEC 60617
identification
identification
IEC 61850-8-1
-
Section 16
ANSI/IEEE C37.2
device number
-
519

Advertisement

Table of Contents
loading