Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 8
Current protection
8.1.7
faultState
I3P
V3P
I3P
ANSI05000740 V1 EN
Figure 80:
Functional overview of OC4PTOC (51/67)
172

Operation principle

The protection design can be decomposed in four parts:
The direction element
The harmonic Restraint Blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.
dirPhAFlt
Direction
Element
dirPhBFlt
dirPhCFlt
Harmonic
harmRestrBlock
Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
The sampled analog phase currents are processed in a pre-processing function block.
Using a parameter setting MeasType within the general settings for the four step phase
1MRK 502 043-UUS B
4 step over current
element
faultState
One element for each
step
en05000740_ansi.vsd
Technical Manual
PICKUP
TRIP