Section 13
Logic
13.3.1.10
376
Default value on all four inputs are logical 1 which makes it possible for the user to
just use the required number of inputs and leave the rest un-connected. The output
OUT has a default value 0 initially, which suppresses one cycle pulse if the function
has been put in the wrong execution order.
Function block
AND
INPUT1
OUT
INPUT2
NOUT
INPUT3
INPUT4
IEC09000289-1-en.vsd
IEC09000289 V1 EN
Figure 179:
AND function block
Signals
Table 260:
AND Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Table 261:
AND Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).

Set-reset memory function block SRMEMORY

Identification
Function description
Set-reset memory function block
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Description
Output signal
Inverted output signal
IEC 61850
IEC 60617
identification
identification
SRMEMORY
1MRK 502 043-UUS B
ANSI/IEEE C37.2
device number
-
-
Technical Manual