Figure 133:
Simplified Pickup and Trip logical diagram of the STEFPHIZ (59THD)
protection
There are two different cases of generator block configuration; with or without
generator circuit breaker. If there is no generator breaker the capacitive coupling to
ground is the same under all operating conditions. When there is a generator breaker,
the capacitive coupling to ground differs between the operating conditions when the
generator is running with the generator breaker open (before synchronization) and with
the circuit breaker closed. This can be shown as in figure 134.
-