Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
8.1.5
Table 68:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
Pickup1
5 - 2500
t1
0.000 - 60.000
TD1
0.05 - 999.00
IMin1
5 - 10000
t1Min
0.000 - 60.000
Table continues on next page
Technical Manual
Name
Type
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
PU_ST3
BOOLEAN
PU_ST4
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
2NDHARM
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
s
0.001
Description
Start signal from step 1
Start signal from step 2
Start signal from step 3
Start signal from step 4
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Block from second harmonic detection
Default
Description
Disabled
Disable/Enable Operation
Non-directional
Directional mode of step 1 off / non-
directional / forward / reverse
ANSI Def. Time
Selection of time delay curve type for step 1
1000
Phase current operate level for step1 in % of
IBase
0.000
Definite time delay of step 1
0.05
Time multiplier for the inverse time delay for
step 1
100
Minimum operate current for step1in% of IBase
0.000
Minimum operate time for inverse curves for
step 1
Section 8
Current protection
169