Phase-Phase And Phase-Neutral Voltage Measurements Vmmxu, Vnmmxu - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
14.1.8.4
14.1.8.5
14.1.9
Technical Manual
outputs and IEC 61850. This is achieved by magnitude and angle compensation at 5,
30 and 100% of rated current. The compensation below 5% and above 100% is
constant and linear in between, see figure 197.
Phase currents (magnitude and angle) are available on the outputs and each magnitude
output has a corresponding supervision level output (Ix_RANGE). The supervision
output signal is an integer in the interval 0-4, see section
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, magnitude and angle) are available on the
outputs and each magnitude output has a corresponding supervision level output
(Vxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section
"Measurement
supervision".
Voltage and current sequence measurements VMSQI, CMSQI
The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, other than
X_RANG, are calculated within the measuring blocks and it is not possible to calibrate
the signals. Input signals are obtained from the pre-processing block and transferred to
corresponding output.
Positive, negative and three times zero sequence quantities are available on the outputs
(voltage and current, magnitude and angle). Each magnitude output has a
corresponding supervision level output (X_RANGE). The output signal is an integer in
the interval 0-4, see section
Technical data
Table 312:
CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU
Function
Voltage
Connected current
Active power, P
Table continues on next page
"Measurement
supervision".
Range or value
(0.1-1.5) ×V
n
(0.2-4.0) × I
n
0.1 x V
< V < 1.5 x V
n
n
0.2 x I
< I < 4.0 x I
n
n
Section 14
Monitoring
"Measurement
supervision".
Accuracy
± 0.5% of V
at V£V
n
n
± 0.5% of V at V > V
n
± 0.5% of I
at I £ I
n
n
± 0.5% of I at I > I
n
± 1.0% of S
at S ≤ S
n
n
± 1.0% of S at S > S
n
421