Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Name
Values (Range)
OperationZ2
Disabled
Enabled
XoffsetZ2
-1000.00 - 1000.00
Z2diameter
0.01 - 3000.00
tZ2
0.00 - 6000.00
Table 49:
LEXPDIS (40) Group settings (advanced)
Name
Values (Range)
DirSuperv
Disabled
Enabled
XoffsetDirLine
-1000.00 - 3000.00
DirAngle
-180.0 - 180.0
Table 50:
LEXPDIS (40) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
7.2.6
7.2.7
Technical Manual
Unit
Step
-
-
%
0.01
%
0.01
s
0.01
Unit
Step
-
-
%
0.01
Deg
0.1
Unit
Step
-
1

Monitored data

Table 51:
LEXPDIS (40) Monitored data
Name
Type
XOHM
REAL
XPERCENT
REAL
ROHM
REAL
RPERCENT
REAL
Operation principle
The Loss of excitation (LEXPDIS ,40) protection in the IED measures the apparent
positive sequence impedance seen out from the generator.
Default
Description
Enabled
Operation Disable/Enable zone Z2
-10.00
Offset of Z2 circle top point along X axis in %
of Zbase
200.00
Diameter of imedance circle for Z2 in % of
Zbase
1.00
Trip time delay for Z2
Default
Description
Disabled
Operation Off/On for additional directional
criterion
0.00
Offset of directional line along X axis in % of
Zbase
-13.0
Angle between directional line and R-axis in
degrees
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
Ohm
-
%
-
Ohm
-
%
Section 7
Impedance protection
Description
Reactance in Primary Ohms
Reactance in percent of Zbase
Resistance in Primary Ohms
Resistance in percent of
Zbase
143