Advertisement

Wiring
5.10 Connecting the motor
Fire after short-circuit in the motor current circuit caused by rotating permanent magnet
synchronous motor
In the event of a short circuit in the converter or in the motor cable, a permanent magnet
synchronous motor supplies energy to the short-circuit as long as the motor is rotating. This can
cause smoke and a fire, endangering people.
• Install a contactor between the motor and the converter and as close to the motor as
• Use a contactor with overvoltage protection to prevent damage to the motor when
• Use converter signal r0863.1 and a free digital output of the converter to open the contactor
5.10.1

Interface description - X2

The motor power interface located on the Wiring Module is available only for the G115D wall-
mounted converter. For a G115D converter with SIMOGEAR geared motor, the wiring between
the converter and the motor is completed when delivered.
Connector variant
Q8/0 connector
X2 - motor power, 8-pin,
female
74
WARNING
possible.
separating the motor from the converter.
between motor and converter in the event of a fault.
Pin
Signal
Description
1
U
Phase U
2
-
Not connected
3
W
Phase W
4
EM-/EM2
EM brake negative (180 V DC) / EM brake 2 (400 V AC)
5
T+
Motor temperature sensor positive
6
EM+/EM1
EM brake positive (180 V DC) / EM brake 1 (400 V AC)
7
V
Phase V
8
T-
Motor temperature sensor negative
9
PE
Protective earth
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA